Description
3 Core Flat: Twin and Earth 2 x7/0.85 (4 mm2) plus 1 x 7/.67 (2.5mmsq) Earth
P.A.C.W. Non-Migratory P.V.C. Insulated and Sheathed.
Building Cable 450/750 volt to AS/NZS 5000.2.
Oxygen-Free Copper.
Non-Migratory 3V90 Sheath 450/750V
Application:
Can be installed in contact with polystyrene and polyurethane.
Includes Caravans, Cold rooms, transportable buildings and in contact with polystyrene wall and roofing insulation materials.
Colour:
Violet
Current Rating
Unenclosed in air: 35
Completely surrounded by thermal insulation: 17
Unenclosed Partially surrounded by insulation: 26
Electrical characteristics
Voltage Drop Single Phase mV/Am at 75°C Laid Flat: 10.59
Voltage Drop Three Phase mV/Am at 75°C Laid Flat: 9.71
Conductor Stranding:
PHASE: 7 strands of 0.85 mm Plain Annealed Copper to AS1125 drawn from Class 102 copper to AS1574.Max. D.C. resistance at 20C: 4.61 ohms / km.
EARTH: 7 strands of 0.67 mm Plain Annealed Copper to AS1125 drawn From Class 102 copper to AS1574.Max. D.C. resistance at 20C: 7.41 ohms / km.
Colour coding:
2 Core - Red, Black
2 Core + Earth - Red, Black, Green/Yellow
Core Insulation:
ACTIVE & NEUTRAL: Coloured Non-Migratory P.V.C. to AS/NZS 3808.
Nominal Diameter: 4.8mm.
Nom. Wall Thickness: 0.8mm.
EARTH: Coloured V90. To AS/NZS 3808.
Nominal Diameter: 3.4mm.
Nom. Wall Thickness: 0.7mm.
Outer Sheath:
Coloured Non-Migratory P.V.C. to AS/NZS 3808. Flat configuration.
Nominal Dimensions: 6.4 x 14.8 mm.
Nom. Wall Thickness: 1.1 mm.
Insulation Resistance:
4.61 ohms / km
Approvals:
AS/NZS 5000.2, AS/NZS 1125, AS/NZS 1574, AS/NZS 3808, RoHS Compliant.